Rinnai · Tankless water heater

25 Condensate pump failure or clogged drain

Medium severity Non-SENSEIRH180 hybridSENSEI RX/CXSENSEI

What the control is telling you

Triggered when the condensate float/safety switch closes because condensate has backed up, or when the accessory condensate pump stops working.

Applies to: SENSEI Series; SENSEI RX/CX Series; Non-SENSEI Series

Likely causes

  • No power to the condensate pump
  • External condensate pump not working
  • Clogged or frozen drain line
  • Loose or damaged wiring between pump/trap and PC board
  • Missing air gap in drain line
  • Restricted condensate trap

Test and repair steps

  1. Confirm the condensate pump has power.
  2. Check that the external (third-party) pump operates correctly.
  3. Make sure the drain line is not clogged or frozen.
  4. Inspect wiring from the pump and from the condensate trap back to the PC board for loose, damaged or broken connections.
  5. Confirm the drain line includes an air gap.
  6. Inspect the condensate trap for restrictions.

Settings for these units

RSC supply connection sizes · SENSEI

ConnectionSize
Gas3/4 in. NPT
Cold inlet3/4 in. NPT
Hot outlet3/4 in. NPT
Condensate drain1/2 in. NPT
Pressure relief valveM33 thread

The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.

Condensate drain line must stay at least 1/2 in. over its whole length.

RSC water quality limits · SENSEI

ContaminantMaximum level
Total hardnessUp to 200 mg/L
AluminumUp to 0.2 mg/L
ChloridesUp to 250 mg/L
CopperUp to 1.0 mg/L
Dissolved CO2Up to 15.0 mg/L
IronUp to 0.3 mg/L
ManganeseUp to 0.05 mg/L
pH6.5 to 8.5
TDSUp to 500 mg/L
ZincUp to 5 mg/L

Damage from water above these limits is not covered by warranty.

Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.

Models that show this code

97 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI

C199eC199iCU160eCU160iCU199eCU199iCX160iCX199iCXP160iCXP199iR50LSiR63LSe2R75LSeR75LSiR94LSeR94LSiR98LSeR98LSe-ASMER98LSiR98LSi-ASMERC80eRC80iRC98eRC98iRE140eRE140iRE160eRE160iRE180eRE180iRE199eRE199iREP160eREP160iREP199eREP199iRH180RL75eRL75e(A)RL75iRL75i(A)RL94eRL94iRLX94iRSC160eRSC160iRSC199eRSC199iRU130eRU130iRU160eRU160iRU180eRU180iRU199eRU199iRU80eRU80iRU90eRU98e

Other codes on the same units

  • 18 Gas valve air/fuel adjustment limit reached
  • 19 Electrical grounding / DC circuit short
  • 21 PC board data transfer error
  • 22 Gas valve adjustment fault
  • 30 Flammable vapor sensor activated or faulty
  • 31 Burner thermocouple out of range
  • 32 Outlet water temperature thermistor fault
  • 33 Heat exchanger thermistor fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.34. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.