Rinnai · Tankless water heater
31 Burner thermocouple out of range
What the control is telling you
Burner thermocouple reading is outside its allowed range: above 30 mV (possible over-firing) or below 8 mV (low gas pressure or low-Btu gas) during combustion.
Applies to: RH180 (Hybrid Tank-Tankless Non-SENSEI Series); Non-SENSEI Series
Likely causes
- Manifold gas pressures set incorrectly for altitude
- DIP switches set incorrectly
- Over-firing from high manifold pressure
- Blocked heat exchanger fins
- Low gas pressure or low Btu gas content
- Failed thermocouple
Test and repair steps
- Check low and high fire manifold pressures and set them for your altitude per the Service Manual or Technical Data Sheet inside the front cover.
- Confirm all PC board DIP switches are set correctly for altitude (see Technical Data Sheet).
- Measure thermocouple output during combustion; normal is 20–27 mV. Code 31 triggers above 30 mV or below 8 mV.
- Above 30 mV verify high fire manifold pressure. If within spec, remove manifold and burners and check heat exchanger fins; clean or replace the heat exchanger if clogged.
- Below 8 mV verify forced low fire gas pressure. If within spec, contact Rinnai Technical Support.
- If the fault persists, replace the thermocouple.
Settings for these units
RUCS/RUS unit clearances · Non-SENSEI
| Location | RUCS indoor to combustibles | RUCS indoor to non-combustibles | RUS outdoor to combustibles | RUS outdoor to non-combustibles |
|---|---|---|---|---|
| Top | 6 in. (152 mm) * | 2 in. (51 mm) * | 12 in. (305 mm) | 2 in. (51 mm) |
| Back | 0 in. | 0 in. | 0 in. | 0 in. |
| Front | 6 in. (152 mm) | 6 in. (152 mm) | - | - |
| Front (panel) | - | - | 24 in. (610 mm) | 0 in. |
| Front (exhaust) | - | - | 24 in. (610 mm) | 24 in. (610 mm) |
| Sides | 2 in. (51 mm) | 1/2 in. (13 mm) | 6 in. (152 mm) | 1/8 in. (3.2 mm) |
| Ground/bottom | 12 in. (305 mm) | 12 in. (305 mm) | 12 in. (305 mm) | 2 in. (51 mm) |
| Vent | 0 in. | 0 in. | - | - |
0 in. from vent components and condensate drain line.
Service clearance 24 in. in front of the heater; closet installs need 6 in. (152 mm) in front.
RUCS/RUS water quality limits · Non-SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg / L |
| Aluminum | Up to 0.2 mg / L |
| Chlorides | Up to 250 mg / L |
| Copper | Up to 1.0 mg / L |
| Dissolved CO2 | Up to 15.0 mg / L or PPM |
| Iron | Up to 0.3 mg / L |
| Manganese | Up to 0.05 mg / L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg / L |
| Zinc | Up to 5 mg / L |
Scale build-up shows as code LC# on a controller (LC on the status monitor without one); flush the heat exchanger.
ScaleCutter parts: 103000038 (system), 103000039 (refill).
Models that show this code
67 models in Non-SENSEI, RH180 hybrid
Other codes on the same units
- 19 Electrical grounding / DC circuit short
- 25 Condensate pump failure or clogged drain
- 30 Flammable vapor sensor activated or faulty
- 32 Outlet water temperature thermistor fault
- 33 Heat exchanger thermistor fault
- 34 Combustion air thermistor (Non-SENSEI) / Lime detecting thermistor (RX/CX)
- 35 Tank temperature sensor fault
- 38 Exhaust gas temperature sensor (CO sensor on RH180)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.36. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.