Rinnai · Tankless water heater
33 Heat exchanger thermistor fault
What the control is telling you
The heat exchanger temperature thermistor or its circuit is reading abnormally.
Applies to: SENSEI Series; SENSEI RX/CX Series; Non-SENSEI Series
Likely causes
- Loose, broken or damaged thermistor harness
- Scale build-up on the thermistor
- Thermistor resistance out of spec
- Failed thermistor
Test and repair steps
- Inspect the thermistor harness from thermistor to PC board for loose, broken or damaged connections.
- Caution: Shut off the water supply and drain the system before continuing.
- With the hot water lines empty, remove the thermistor and clean off any scale or deposits.
- With a meter set to read 20K ohms, measure across the thermistor plug; resistance should drop when the bulb is warmed and rise when cooled.
- Typical values 11.4–14K ohms at 59°F, 6.4–7.8K at 86°F, 3.6–4.5K at 113°F, 2.2–2.7K at 140°F, 0.6–0.8K at 221°F.
- If readings are good, reinstall the thermistor, checking that its small O-ring is intact and lightly lubricated.
- Restore water supply and check for leaks at the thermistor.
- Fire the unit again; if code 33 returns, replace the thermistor.
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
97 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI
Other codes on the same units
- 25 Condensate pump failure or clogged drain
- 30 Flammable vapor sensor activated or faulty
- 31 Burner thermocouple out of range
- 32 Outlet water temperature thermistor fault
- 34 Combustion air thermistor (Non-SENSEI) / Lime detecting thermistor (RX/CX)
- 35 Tank temperature sensor fault
- 38 Exhaust gas temperature sensor (CO sensor on RH180)
- 41 Freeze protection / outdoor air temperature sensor fault
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.38. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.