Rinnai · Tankless water heater
22 Gas valve adjustment fault
What the control is telling you
Fault with gas valve adjustment, typically linked to the front reed switch position or incorrect gas valve parameters.
Applies to: SENSEI RX/CX Series
Likely causes
- Reed switch on front of gas valve not positioned correctly
- Incorrect gas valve parameters
Test and repair steps
- Confirm the reed switch on the front of the gas valve is seated in its correct location.
- Check all gas valve parameters; if any are wrong, re-enter them per the Gas Valve Replacement Instructions (100000855).
Settings for these units
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
- RX temperature settings available · SENSEI RX/CX
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.