Rinnai · Tankless water heater
16 Outlet water over-temperature safety shutdown
What the control is telling you
Safety shutdown triggered because the outgoing water temperature went above 203°F (95°C).
Applies to: SENSEI Series; SENSEI RX/CX Series; Non-SENSEI Series
Likely causes
- Restricted air flow at the vent terminal
- Fan not operating properly
- Check valve behind fan motor stuck and restricting air flow
- Debris in combustion chamber or exhaust piping
- Blocked heat exchanger
- Unit set to wrong gas type (e.g. Parameter 10 incorrect)
- Faulty gas valve or fan motor assembly
Test and repair steps
- Look for anything restricting air flow around the vent terminal.
- Confirm the fan operates correctly.
- Make sure the check valve behind the fan motor is not stuck and blocking air flow.
- Check the combustion chamber and exhaust piping for foreign material.
- Check the heat exchanger for blockage.
- Confirm the unit is configured for the gas type on its rating plate.
- SENSEI / SENSEI RX/CX Check Parameter 10 (A = Natural Gas, B = Propane). On RX/CX models, Parameter 10 can only be changed within 20 minutes of a power reset.
- If the fault persists, replace the gas valve assembly, then the fan motor assembly if needed.
Settings for these units
RSC supply connection sizes · SENSEI
| Connection | Size |
|---|---|
| Gas | 3/4 in. NPT |
| Cold inlet | 3/4 in. NPT |
| Hot outlet | 3/4 in. NPT |
| Condensate drain | 1/2 in. NPT |
| Pressure relief valve | M33 thread |
The PRV and its adapter come in the box; PRV must be rated 150 psi and at least the heater Btu/h.
Condensate drain line must stay at least 1/2 in. over its whole length.
RSC water quality limits · SENSEI
| Contaminant | Maximum level |
|---|---|
| Total hardness | Up to 200 mg/L |
| Aluminum | Up to 0.2 mg/L |
| Chlorides | Up to 250 mg/L |
| Copper | Up to 1.0 mg/L |
| Dissolved CO2 | Up to 15.0 mg/L |
| Iron | Up to 0.3 mg/L |
| Manganese | Up to 0.05 mg/L |
| pH | 6.5 to 8.5 |
| TDS | Up to 500 mg/L |
| Zinc | Up to 5 mg/L |
Damage from water above these limits is not covered by warranty.
Hard water should be treated; use the Service Soon (SS) reminder (parameter 03) for flushing intervals.
- RSC clearances to combustibles · SENSEI
- RSC temperature settings available · SENSEI
- RX supply connection sizes · SENSEI RX/CX
- RX water quality limits · SENSEI RX/CX
- RX water treatment and flushing by hardness · SENSEI RX/CX
- RX clearances to combustibles · SENSEI RX/CX
Models that show this code
97 models in Non-SENSEI, RH180 hybrid, SENSEI RX/CX, SENSEI
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting TWH Diagnostic Codes (100000652), p.27. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.