NTI · Boiler
NOAVL PCB error: boiler application not set
What the control is telling you
Parameter 046 is set to UNDEF. Clears once the issue is corrected.
Applies to: TRX150
Likely causes
- Parameter 046 left at UNDEF
- Short on the eBus2 wires
Test and repair steps
- Set parameter 046 for the boiler application: b--SIN for single boiler (default), b--MAS for cascade master, b--FL1 to b--FL7 for cascade followers 1 to 7.
- If the problem continues, check the eBus2 wires and make sure they are not shorted together.
- If the problem still continues, replace the main control.
Models that show this code
5 models in TRX
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 87. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.