NTI · Boiler
EMERG Incorrect wiring to BUS connection (emergency mode)
What the control is telling you
The control sensed a short on the BUS connection. The boiler runs CH in emergency mode with a 113 °F target. The emergency setpoint can be changed with parameter 2.10.3.
Applies to: TRX150
Likely causes
- Short circuit on BUS wiring
- Wrong polarity on room sensor or zone controller
- Incorrect daisy-chain wiring in a cascade
Test and repair steps
- Disconnect the field wiring from the BUS connection.
- If an NTI room sensor or zone controller is connected to BUS, check polarity and look for shorts.
- If the boiler is part of a cascade, check the daisy-chain wiring between the BUS connection of each boiler.
Models that show this code
5 models in TRX
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 87. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.