FILL - 108 Low water pressure lockout

High severity TRX

What the control is telling you

If water pressure drops below 7 PSI, the control shows this blocking error and stops burner operation.

Applies to: TRX150, TRX199, TRX199C

Likely causes

  • Water pressure in the system drops below 7 PSI

Test and repair steps

  1. Refill the system to bring water pressure back above 7 PSI.
  2. Check for leaks before and after refilling.

Models that show this code

5 models in TRX

TRX085TRX110CTRX150TRX199TRX199C

Other codes on the same units

  • 5 P3 Flame loss during run
  • 5 P6 3rd and 4th ignition failed
  • 06 02 Exhaust temperature above 204 °F (96 °C)
  • 06 03 APS open
  • 06 05 Exhaust NTC circuit open or short circuit
  • 6 12 Insufficient fan speed
  • EMERG Incorrect wiring to BUS connection (emergency mode)
  • NOAVL PCB error: boiler application not set

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: NTI TRX150 manual, p. 31. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.