NTI · Boiler
FILL - 108 Low water pressure lockout
What the control is telling you
If water pressure drops below 7 PSI, the control shows this blocking error and stops burner operation.
Applies to: TRX150, TRX199, TRX199C
Likely causes
- Water pressure in the system drops below 7 PSI
Test and repair steps
- Refill the system to bring water pressure back above 7 PSI.
- Check for leaks before and after refilling.
Models that show this code
5 models in TRX
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: NTI TRX150 manual, p. 31. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.