E130 Main panel to power board communication fault
What the control is telling you
Fault in the connection between the main panel and the power board.
Applies to: WEC600
Likely causes
- Loose or faulty harness between main panel and power board
- Faulty PCB
- Faulty power assembly
Test and repair steps
- Check the harness connection between the main panel and the power board.
- If the harness is connected, replace the harness.
- If the error occurs, replace the PCB.
- If it occurs again, replace the power assembly.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien WEC service manual, p. 72. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.