Navien · General

E116 Input voltage high

Medium severity WEC Series

What the control is telling you

Input voltage is above the allowed level.

Applies to: WEC600

Likely causes

  • Input voltage above 132 V
  • Faulty power assembly

Test and repair steps

  1. Monitor whether the error occurs continuously.
  2. Measure the input voltage with a multimeter.
  3. If the input voltage is above 132 V, adjust it to 120 V with a transformer.
  4. If the voltage is below 132 V, replace the power assembly.

Other codes on the same units

  • E106 PCB or harness fault
  • E107 PCB or harness fault
  • E110 Power unit overheating
  • E111 - E115 Temporary power unit fault
  • E117 Input voltage low
  • E118 Input frequency high
  • E119 Input frequency low
  • E122 Heat sink sensor fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien WEC service manual, p. 70. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.