Navien · General
E119 Input frequency low
What the control is telling you
Input frequency is below the allowed level.
Applies to: WEC600
Likely causes
- Input frequency below 57.6 Hz
- Faulty power assembly
Test and repair steps
- Monitor whether the error occurs continuously.
- Measure the input frequency with a multimeter.
- If the frequency is below 57.6 Hz, adjust it to 60 Hz with a frequency inverter.
- If the frequency is above 57.6 Hz, replace the power assembly.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien WEC service manual, p. 71. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.