Navien · General
022 Regeneration line open
What the control is telling you
Regeneration solenoid valve open fault (valve 2).
Applies to: WEC600
Likely causes
- Regeneration solenoid valve
Test and repair steps
- Check inlet pressure is 36.3-74 psi (250-510 kPa).
- Clear with ErSt, check drain outlet in Standby, then recheck.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien WEC service manual, p. 53. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.