010 High water pressure

Medium severity WEC Series

What the control is telling you

Feedwater pressure is above the limit.

Applies to: WEC600

Likely causes

  • Feedwater pressure above 74 psi (510 kPa)

Test and repair steps

  1. Measure feedwater pressure.
  2. If above 74 psi (510 kPa), install a pressure regulator.
  3. Clear automatically or by power cycle once below 74 psi.

Other codes on the same units

  • 001 Water leakage
  • 002 Water outage
  • 003 Water outage during CIP
  • 020 Product flow path clogged
  • 021 Regeneration line open
  • 022 Regeneration line open
  • 023 Bypass line clogged
  • 024 Regeneration line clogged

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien WEC service manual, p. 52. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.