Navien · General
020 Product flow path clogged
What the control is telling you
Flow path blocked, bypass valve or water outage.
Applies to: WEC600
Likely causes
- Low inlet pressure
- No water supply
Test and repair steps
- Confirm the house has water.
- Check inlet pressure is 36.3-74 psi (250-510 kPa), raise if low.
- Clear with ErSt or Install Check Mode; call service if it repeats.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien WEC service manual, p. 52-53. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.