E278 External (system) supply sensor not detected
What the control is telling you
The system supply sensor is not detected. Occurs when the heating control method is set to system supply temperature. NFC-H manual lists the reset type as: Alarm.
Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)
Likely causes
- System sensor not installed or disconnected
- Wiring fault
- Control method set to Sys Supply without a sensor
Test and repair steps
- Check Status Information > 8. Sys Supply Temp.
- Check the system sensor wiring at the PCB.
- Without a system sensor, go to Space Htg Operation > 5. SH Control Method and pick Supply or Return Temperature.
- Code keeps returning? Phone Navien Technical Support, 1-800-519-8794.
Settings for these units
- Minimum installation clearances (indoor) · Navien NCB-H
- Water quality limits (DHW and system fill) · Navien NCB-H
- Minimum installation clearances (indoor) · Navien NFC-H
- Water quality limits (DHW and system fill) · Navien NFC-H
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.