Navien · Combi boiler
E109 Fan motor fault
What the control is telling you
The combustion fan is not reaching or holding the target speed. NFC-H manual lists the reset type as: Manual reset.
Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)
Likely causes
- Clogged air intake filter
- Fan wiring
- Failed fan motor
Test and repair steps
- Clean the air intake filter (the manual's listed remedy).
- Compare Status Information 18. Fan Target RPM with 19. Fan Current RPM.
- Run Test Mode > 1. Fan Motor to ramp the fan up and down.
- Check the fan connector and wiring.
- Code keeps returning? Phone Navien Technical Support, 1-800-519-8794.
Settings for these units
Minimum installation clearances (indoor) · Navien NCB-H
| Side | Minimum |
|---|---|
| Top | 9 in (229 mm) |
| Back | 0.5 in (13 mm) |
| Front | 4 in (100 mm) |
| Sides | 3 in (76 mm) |
| Bottom | 12 in (300 mm) |
Indoor wall-hung only; ambient must stay above 32°F (0°C).
Do not install on carpet; leave room for service.
Water quality limits (DHW and system fill) · Navien NCB-H
| Contaminant | Max allowed |
|---|---|
| Total hardness | 200 mg/l (12 grains/gallon) |
| Aluminum | 0.05 to 0.2 mg/l |
| Chloride | 250 mg/l |
| Copper | 1.0 mg/l |
| Iron | 0.3 mg/l |
| Manganese | 0.05 mg/l |
| pH | 6.5 to 8.5 |
| Sulfate | 250 mg/l (DHW table); 205 mg/l (fill table) |
| Total dissolved solids | 500 mg/l |
| Zinc | 5 mg/l |
| Chlorine (fill water) | 4 mg/l |
Scale damage from poor water is not covered by warranty.
Manual shows sulfate 250 mg/l on p.23 and 205 mg/l on p.29 - check local guidance.
- Minimum installation clearances (indoor) · Navien NFC-H
- Water quality limits (DHW and system fill) · Navien NFC-H
Models that show this code
7 models in Navien NCB-H, Navien NFC-H
Other codes on the same units
- E046 Heat exchanger thermistor / overheat sensor fault
- E047 Exhaust thermistor fault
- E060 Dual venturi fault
- E110 Exhaust blockage / abnormal air pressure (APS)
- E205 Heating supply temperature sensor fault
- E218 Heating return temperature sensor fault
- E278 External (system) supply sensor not detected
- E279 External (system) return sensor not detected
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.