Navien · Combi boiler

E046 Heat exchanger thermistor / overheat sensor fault

Medium severity Navien NCB-HNavien NFC-H

What the control is telling you

The heat exchanger temperature sensor reading is abnormal (open or short). NFC-H manual lists the reset type as: Auto reset.

Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)

Likely causes

  • Loose or damaged sensor wiring/connector
  • Failed sensor

Test and repair steps

  1. Power off and check the heat exchanger sensor connector and wiring.
  2. Check Menu > 4. Error History (last 10 errors) to see how often the code has occurred.
  3. Code keeps returning? Phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Minimum installation clearances (indoor) · Navien NCB-H

SideMinimum
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)

Indoor wall-hung only; ambient must stay above 32°F (0°C).

Do not install on carpet; leave room for service.

Water quality limits (DHW and system fill) · Navien NCB-H

ContaminantMax allowed
Total hardness200 mg/l (12 grains/gallon)
Aluminum0.05 to 0.2 mg/l
Chloride250 mg/l
Copper1.0 mg/l
Iron0.3 mg/l
Manganese0.05 mg/l
pH6.5 to 8.5
Sulfate250 mg/l (DHW table); 205 mg/l (fill table)
Total dissolved solids500 mg/l
Zinc5 mg/l
Chlorine (fill water)4 mg/l

Scale damage from poor water is not covered by warranty.

Manual shows sulfate 250 mg/l on p.23 and 205 mg/l on p.29 - check local guidance.

Models that show this code

7 models in Navien NCB-H, Navien NFC-H

NCB-190/060HNCB-190/080HNCB-240/110HNCB-240/130HNCB-250/150HNFC-250/175HNFC-250/200H

Other codes on the same units

  • E030 Exhaust overheat (abnormal exhaust temperature)
  • E031 Burner overheat
  • E047 Exhaust thermistor fault
  • E060 Dual venturi fault
  • E109 Fan motor fault
  • E110 Exhaust blockage / abnormal air pressure (APS)
  • E205 Heating supply temperature sensor fault
  • E218 Heating return temperature sensor fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.