Navien · Combi boiler

E352 High water pressure

High severity Navien NCB-HNavien NFC-H

What the control is telling you

System water pressure is above the allowed limit. NFC-H manual lists the reset type as: Auto reset.

Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)

Likely causes

  • Waterlogged or undersized expansion tank
  • Fill valve passing
  • Overheating

Test and repair steps

  1. Check Status Information > 16. Water Pressure.
  2. Check the expansion tank pre-charge and size.
  3. Check the fill/auto-feed valve is not leaking through.
  4. NFC-H check the 17. High Sys Pressure parameter (default 50 psi, cannot be below 40 psi).
  5. Code keeps returning? Phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.