Navien · Combi boiler

E302 Low water pressure (internal LWCO)

High severity Navien NFC-H

What the control is telling you

NFC-H only: the built-in pressure-type low water cutoff sees insufficient water in the boiler (minimum operating pressure 6 psi by default). Needs a manual reset. This code is mentioned in the LWCO section but is not in the manual's error code table.

Applies to: Navien NFC-H fire-tube combi boilers (NFC-250/175H, 250/200H)

Likely causes

  • Low system pressure / leak
  • Make-up water supply closed
  • Auto-fill not working

Test and repair steps

  1. Check system pressure (Status Information > 16. Water Pressure) and look for leaks or a discharging relief valve.
  2. Make sure make-up water to the boiler is open and the Auto-Fill Pressure parameter is set correctly (12-50 psi, default 12 psi).
  3. Refill and purge air.
  4. Reset from the front panel by pressing the Back button, then confirm the code clears.
  5. Code keeps returning? Phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NFC-H Installation Manual, 3.1 Internal LWCO note, p.23. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.