Navien · Boiler

E016 Heat exchanger overheat (check flow / system filters)

High severity Navien NHB-HNavien NFB-H

What the control is telling you

Heat exchanger temperature too high. Manual action: check flow and clean system filters.

Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers

Likely causes

  • Low water flow
  • Dirty system filter or strainer
  • Air in system
  • Scaled heat exchanger

Test and repair steps

  1. Warning: If overheating occurs, close the manual gas valve but keep the circulator powered.
  2. Confirm the boiler pump runs (Test Mode > Boiler Pump) and that all isolation valves are fully open; the manual requires full-port ball valves.
  3. Check the flow against the pump sizing table: e.g. at 20°F ΔT NHB-055H needs 5 GPM @ 7.2 ft, NHB-150H 13.5 GPM @ 19.8 ft; NFB-175H 16 GPM @ 4.2 ft, NFB-200H 18 GPM @ 5.3 ft (see Specs). With glycol use the corrected glycol values.
  4. NFB-H only flow through the boiler must stay between the minimum 7.0/8.0 GPM and maximum 23.1/26.4 GPM (175H/200H).
  5. Purge air from the boiler and system (Air Purge Mode, air vent cap fully removed during fill) and check the air separator.
  6. Clean the strainer/filter in the system return; debris restricts flow.
  7. Primary/secondary piping closely spaced tees no more than 4 pipe diameters or 12 in apart.
  8. Compare supply and return temperatures in Status Info; a large rise points to low flow. Check Service Status Info for the HEX overheat count.
  9. If scale is suspected, check water quality (hardness up to 200 mg/l, pH 6.5-8.5) and flush the heat exchanger per the User's Information Manual.

Settings for these units

Installation clearances (indoor) · Navien NHB-H

SideMinimum clearance
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)
Vent to combustibles0 in

Bracket gives 5/8 in (16 mm) from the wall; studs at 16 in on centre.

Common vent installs: 36 in above the top and 24 in in front are recommended for service.

Installation clearances (indoor) · Navien NFB-H

SideMinimum clearance
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)
Vent to combustibles0 in

Do not install on carpet; indoors only.

Remove the wood pallet and refit the 6 screws to keep the cabinet airtight.

Models that show this code

6 models in Navien NHB-H, Navien NFB-H

NFB-175HNFB-200HNHB-055HNHB-080HNHB-110HNHB-150H

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.