Navien · Boiler
E012 Flame loss
What the control is telling you
The flame went out during operation. Manual action: check gas, venting and the condensate trap.
Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers
Likely causes
- Low or unstable gas pressure
- Blocked or over-length vent / intake
- Condensate trap empty, blocked or backing up
- Dirty flame rod
- Wrong orifice or combustion setting
Test and repair steps
- Check inlet gas pressure at maximum fire NG 3.5-10.5 in WC, LP 8.0-13.0 in WC.
- Inspect the exhaust and intake for blockage, snow, separated joints, and verify length/elbows are within limits (2 in: 65 ft, 3 in: 150 ft; 90° = 8 ft / 5 ft).
- Check the condensate line slopes down at least 1/4 in per ft, is not frozen, and the trap is filled with water.
- Clean the flame rod and check the Flame Loss count in Service Status Info.
- Check the air intake filter for lint/dust.
- Verify CO2 at low and high fire against the combustion table; at high fire never adjust the valve - check the orifice instead.
Settings for these units
Installation clearances (indoor) · Navien NHB-H
| Side | Minimum clearance |
|---|---|
| Top | 9 in (229 mm) |
| Back | 0.5 in (13 mm) |
| Front | 4 in (100 mm) |
| Sides | 3 in (76 mm) |
| Bottom | 12 in (300 mm) |
| Vent to combustibles | 0 in |
Bracket gives 5/8 in (16 mm) from the wall; studs at 16 in on centre.
Common vent installs: 36 in above the top and 24 in in front are recommended for service.
Installation clearances (indoor) · Navien NFB-H
| Side | Minimum clearance |
|---|---|
| Top | 9 in (229 mm) |
| Back | 0.5 in (13 mm) |
| Front | 4 in (100 mm) |
| Sides | 3 in (76 mm) |
| Bottom | 12 in (300 mm) |
| Vent to combustibles | 0 in |
Do not install on carpet; indoors only.
Remove the wood pallet and refit the 6 screws to keep the cabinet airtight.
Models that show this code
6 models in Navien NHB-H, Navien NFB-H
Other codes on the same units
- 4th ignition - No. of Times EMS Data counter 6
- 5~10th ignition - No. of Times EMS Data counter 7
- E001 Heat exchanger overheat
- E003 Ignition failure
- E004 False flame detected
- E016 Heat exchanger overheat (check flow / system filters)
- E030 Exhaust overheat
- E031 Burner overheat
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.