Navien · Boiler
E003 Ignition failure
What the control is telling you
The burner did not light during the ignition attempts. Manual action: check the gas supply valve and the igniter.
Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers
Likely causes
- Manual gas valve closed or gas supply interrupted
- Inlet gas pressure outside the allowed range
- Gas type DIP switch or orifice does not match the gas supplied
- Dirty or damaged igniter / flame rod, poor ignition ground
- Blocked air intake filter, vent or condensate trap
Test and repair steps
- Make sure the manual gas valve is open and other gas appliances have gas.
- Measure inlet gas pressure with the boiler at maximum fire (Special Operations > 2nd MAX): NG 3.5-10.5 in WC, LP 8.0-13.0 in WC (NHB-H spec table lists LP max 13.5 in WC).
- Confirm DIP SW2 #1 matches the gas (OFF = NG, ON = LP) and that the correct orifice / conversion kit is installed for the gas and altitude.
- Purge air from a new gas line before the first start (the manual has you run space heating until it shuts down from lack of gas, then restart).
- Warning: Turn off power and gas. Remove and clean the igniter and flame rod; replace if they cannot be cleaned, and check the gasket.
- Check the ignition ground wire is tight to the casing and has continuity.
- Check the air intake filter, vent terminations and condensate trap (filled with water and draining).
- Check the ignition attempt counters in Service Status Info, then verify CO2 against the combustion table after repairs.
Settings for these units
Installation clearances (indoor) · Navien NHB-H
| Side | Minimum clearance |
|---|---|
| Top | 9 in (229 mm) |
| Back | 0.5 in (13 mm) |
| Front | 4 in (100 mm) |
| Sides | 3 in (76 mm) |
| Bottom | 12 in (300 mm) |
| Vent to combustibles | 0 in |
Bracket gives 5/8 in (16 mm) from the wall; studs at 16 in on centre.
Common vent installs: 36 in above the top and 24 in in front are recommended for service.
Installation clearances (indoor) · Navien NFB-H
| Side | Minimum clearance |
|---|---|
| Top | 9 in (229 mm) |
| Back | 0.5 in (13 mm) |
| Front | 4 in (100 mm) |
| Sides | 3 in (76 mm) |
| Bottom | 12 in (300 mm) |
| Vent to combustibles | 0 in |
Do not install on carpet; indoors only.
Remove the wood pallet and refit the 6 screws to keep the cabinet airtight.
Models that show this code
6 models in Navien NHB-H, Navien NFB-H
Other codes on the same units
- 2nd ignition - No. of Times EMS Data counter 4
- 3rd ignition - No. of Times EMS Data counter 5
- 4th ignition - No. of Times EMS Data counter 6
- 5~10th ignition - No. of Times EMS Data counter 7
- E001 Heat exchanger overheat
- E004 False flame detected
- E012 Flame loss
- E016 Heat exchanger overheat (check flow / system filters)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.