Navien · Boiler

E004 False flame detected

High severity Navien NHB-HNavien NFB-H

What the control is telling you

The control sees a flame signal when there should be no flame. Manual action: check the electrical ground.

Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers

Likely causes

  • Poor or missing electrical ground
  • Contaminated, wet or shorted flame rod
  • Gas valve not closing fully (flame present after shutdown)

Test and repair steps

  1. Verify the boiler is plugged into a properly grounded outlet, or if hard-wired that ground is not taken from gas or water piping.
  2. Check the ignition ground wire at the casing and test ground continuity with a meter.
  3. Check polarity of the power supply connection.
  4. Read the Flame Value in Status Info 70 or less means flame on, 175 or more means flame off. A low value with the burner off confirms a false signal.
  5. Warning: Power off. Inspect and clean the flame rod and its wire; replace if damaged.
  6. Warning: If flame stays on after the call ends, shut the manual gas valve and replace the gas valve.

Settings for these units

Installation clearances (indoor) · Navien NHB-H

SideMinimum clearance
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)
Vent to combustibles0 in

Bracket gives 5/8 in (16 mm) from the wall; studs at 16 in on centre.

Common vent installs: 36 in above the top and 24 in in front are recommended for service.

Installation clearances (indoor) · Navien NFB-H

SideMinimum clearance
Top9 in (229 mm)
Back0.5 in (13 mm)
Front4 in (100 mm)
Sides3 in (76 mm)
Bottom12 in (300 mm)
Vent to combustibles0 in

Do not install on carpet; indoors only.

Remove the wood pallet and refit the 6 screws to keep the cabinet airtight.

Models that show this code

6 models in Navien NHB-H, Navien NFB-H

NFB-175HNFB-200HNHB-055HNHB-080HNHB-110HNHB-150H

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.