Navien · Air conditioner
FA Outdoor board memory (EEPROM) fault
What the control is telling you
A chip on the outdoor PCB has failed. There is nothing to adjust in the field.
Applies to: NAA17V36 (24K/36K), NAA17V60 (48K/60K)
Likely causes
- Defective outdoor PCB
Test and repair steps
- Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
- Replace the outdoor PCB.
Models that show this code
2 models in Navien NAA
Other codes on the same units
- ATL Outdoor temperature outside operating range
- FB Drive chip memory (EEPROM) fault
- FC Drive module temperature sensor fault
- FD Pressure sensor not detected
- FE T3 or T5 probe out of position
- FF High pressure switch reads open all the time
- HC Lockout: discharge probe off the pipe (FE repeated)
- HE Repeated condensate-risk faults (F8)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NAA Series Air Conditioner Service Manual, 3.2.4, p.25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.