Navien · Air conditioner

FF High pressure switch reads open all the time

High severity Navien NAA

What the control is telling you

The high pressure switch input stays open, even at rest.

Applies to: NAA17V36 (24K/36K), NAA17V60 (48K/60K)

Likely causes

  • Switch plug loose
  • Failed high pressure switch
  • Outdoor PCB fault

Test and repair steps

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Reseat the high pressure switch plug.
  3. Jumper the HPS port on the board (jumper cap, or a screwdriver across the two pins) and power the unit back up.
  4. Code clears with the jumper replace the pressure switch. Remove the jumper.
  5. Code stays with the jumper replace the outdoor PCB.

Models that show this code

2 models in Navien NAA

NAA17V36NAA17V60

Other codes on the same units

  • FA Outdoor board memory (EEPROM) fault
  • FB Drive chip memory (EEPROM) fault
  • FC Drive module temperature sensor fault
  • FD Pressure sensor not detected
  • FE T3 or T5 probe out of position
  • HC Lockout: discharge probe off the pipe (FE repeated)
  • HE Repeated condensate-risk faults (F8)
  • LA Compressor speed held back by voltage

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAA Series Air Conditioner Service Manual, 3.2.8, p.27. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.