Navien · Air conditioner

HE Repeated condensate-risk faults (F8)

Medium severity Navien NAA

What the control is telling you

F8 happened 3 times within 60 minutes. Same checks as F8.

Applies to: NAA17V36 (24K/36K), NAA17V60 (48K/60K)

Likely causes

  • T4 or T7 sensor out of range
  • PCB reading the sensors wrong

Test and repair steps

  1. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  2. Check T4 and T7 resistance against the 6.3 R-T Table, p.61.
  3. Compare the CHK readings with a thermometer. Replace the outdoor PCB if they disagree with good sensors.

Models that show this code

2 models in Navien NAA

NAA17V36NAA17V60

Other codes on the same units

  • FC Drive module temperature sensor fault
  • FD Pressure sensor not detected
  • FE T3 or T5 probe out of position
  • FF High pressure switch reads open all the time
  • HC Lockout: discharge probe off the pipe (FE repeated)
  • LA Compressor speed held back by voltage
  • LB Compressor speed held back by high pressure
  • LC Compressor speed held back by condenser temperature

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAA Series Air Conditioner Service Manual, 3.2.2, p.23. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.