Navien · Air conditioner

ATL Outdoor temperature outside operating range

Medium severity Navien NAA

What the control is telling you

The T4 outdoor sensor reads outside the operating range (5 to 125°F (-15 to 52°C)). The unit waits.

Applies to: NAA17V36 (24K/36K), NAA17V60 (48K/60K)

Likely causes

  • Real outdoor temperature outside the range
  • T4 sensor reading wrong
  • PCB fault

Test and repair steps

  1. Check the real outdoor temperature. Outside the range: wait for it to come back in.
  2. Temperature is normal check parameter 07 (T4) on the CHK display.
  3. Power off at the disconnect and wait for the inverter board to discharge before touching wiring or the PCB.
  4. Display reads out of range on a normal day: check the T4 plug and resistance (6.3 R-T Table, p.61) and replace the sensor.
  5. Sensor good replace the outdoor PCB.

Models that show this code

2 models in Navien NAA

NAA17V36NAA17V60

Other codes on the same units

  • FA Outdoor board memory (EEPROM) fault
  • FB Drive chip memory (EEPROM) fault
  • FC Drive module temperature sensor fault
  • FD Pressure sensor not detected
  • FE T3 or T5 probe out of position
  • FF High pressure switch reads open all the time
  • HC Lockout: discharge probe off the pipe (FE repeated)
  • HE Repeated condensate-risk faults (F8)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NAA Series Air Conditioner Service Manual, 3.2.21, p.45. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.