TEST RUN (wireless remote) Wireless remote test run

Menu / mode display Mr. Slim PEAD-RP JA(L) ducted indoor unit

What the display is showing

Test run lets you check cooling and heating without waiting for a thermostat call. TEST RUN and the current operation mode appear on the display. FAN, DRY and AUTO modes cannot be run in test run. Aim the remote at the indoor unit receiver throughout.

Applies to: Mr. Slim PEAD-RP JA(L) ducted indoor units with PAR-21MAA wired remote

What to do

  1. Power the unit at least 12 hours ahead of the test run.
  2. Start with the remote display off; press the TEST RUN button twice in a row.
  3. Press MODE to select COOL and confirm cold air; press MODE again for HEAT and confirm warm air.
  4. Press FAN to check the fan speed changes and VANE to check the auto vane moves.
  5. Press ON/OFF to stop the test run.

Models that show this code

14 models in Mr. Slim PEAD-RP JA(L) ducted indoor unit

PEAD-RP100JAPEAD-RP100JALPEAD-RP125JAPEAD-RP125JALPEAD-RP140JAPEAD-RP140JALPEAD-RP35JAPEAD-RP35JALPEAD-RP50JAPEAD-RP50JALPEAD-RP60JAPEAD-RP60JALPEAD-RP71JAPEAD-RP71JAL

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Mitsubishi PEAD-RP35JA(L) Service Manual, 10-2 Self-Check Function, Test run, p.28. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.