Mitsubishi · Heat pump

Self-check (wired remote) Remote controller self-check mode

Menu / mode display Mr. Slim PEAD-RP JA(L) ducted indoor unit

What the display is showing

Shows the error history as check codes on the wired remote LCD (P1, E6, etc.). Use it to read the last fault, not to run the unit. In a system-control installation the refrigerant address of the indoor/outdoor unit must be chosen first.

Applies to: Mr. Slim PEAD-RP JA(L) ducted indoor units with PAR-21MAA wired remote

What to do

  1. Turn the power on.
  2. Press the CHECK button twice.
  3. If system control is used, set the refrigerant address with the TEMP buttons.
  4. Read the check code on the LCD.
  5. End the self-check with the ON/OFF button.

Models that show this code

14 models in Mr. Slim PEAD-RP JA(L) ducted indoor unit

PEAD-RP100JAPEAD-RP100JALPEAD-RP125JAPEAD-RP125JALPEAD-RP140JAPEAD-RP140JALPEAD-RP35JAPEAD-RP35JALPEAD-RP50JAPEAD-RP50JALPEAD-RP60JAPEAD-RP60JALPEAD-RP71JAPEAD-RP71JAL

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Mitsubishi PEAD-RP35JA(L) Service Manual, 10-2 Self-Check Function, p.27. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.