Majestic · Gas fireplace
1 RED / 2 sec (until reset) Pressure switch failure (power vent only)
What the control is telling you
Single red flash every 2 seconds until manual reset. Applies only to power vent versions.
Applies to: Power vent versions of the SC7 control
Likely causes
- Pressure switch did not prove on a power vent unit
Test and repair steps
- Check the vent system for blockage
- Check the pressure switch and its wiring
- Reset by cycling the master switch OFF then ON
Other codes on the same units
- 1 BEEP Single beep (confirmation)
- 1 GREEN / 2 sec Pilot lockout - trial for ignition
- 1 RED Conversion cover missing
- 1 RED / 10 sec Low battery
- 1 RED-GREEN / 2 sec Pilot lockout - flame loss
- 2 BEEPS Double beep (confirmation)
- 2 RED Spark fail
- 2 RED / 10 sec No or low thermopile power
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Majestic DVBL7 Series Installation and Operating Instructions, p. 41. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.