Majestic · Gas fireplace

2 RED / 10 sec No or low thermopile power

Medium severity DVBL7 Signature Command

What the control is telling you

Two red flashes every 10 seconds, continuously.

Applies to: 300DVBLN/PSC7, 400DVBLN/PSC7, 500DVBLN/PSC7 (Signature Command)

Likely causes

  • Thermopile not producing enough voltage
  • Pilot flame not reaching the thermopile

Test and repair steps

  1. Check the pilot flame is reaching the thermopile
  2. Check the black and red thermopile connections at the control board
  3. Replace the pilot assembly if the thermopile is weak

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Majestic DVBL7 Series Installation and Operating Instructions, p. 41, p. 50. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.