Lifebreath · Hrv

Repeater LED red Wireless repeater: no link to main control

Medium severity RNC

What the control is telling you

Red on the 99-RX02 means it has lost the main wall control. Wireless timers that go through it will not bring the HRV to high speed.

Applies to: 99-RX02 wireless repeater

Likely causes

  • Repeater too far from the main wall control
  • Repeater placed in a spot with too many obstructions

Test and repair steps

  1. Unplug it and plug it into a 120 V outlet closer to the main wall control.
  2. Watch the LED. Move it until you get solid or flashing green.
  3. Aim for about halfway between the wireless timer and the main control.

Settings for these units

HRV maintenance intervals · RNC

ItemHow often
Outside hoods and bird screenMonthly (more in winter for snow and frost)
Filters (washable)4 times a year
CoreTwice a year
MotorsNo maintenance
Condensate drain line and P-trapOnce a year
DuctworkOnce a year if needed
Inside of cabinet wipe-downTwice a year

Turn off power at the disconnect before any service.

Models that show this code

1 model in RNC

RNC5-ES

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lifebreath RNC5-ES Homeowner's Guide (69-RNC5-OWNERS 012616), Timers, Repeater - 99-RX02, p. 11. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.