Lifebreath · Hrv
Dehumidistat light steady Dehumidistat satisfied
What the display is showing
Light stays on solid on the BC02 or BC03 a few seconds after setting. It means humidity is below the set point and the dehumidistat is not calling. Normal.
Applies to: 99-BC02, 99-BC03 wall controls
Good to know
- Indoor humidity is below the set point
What to do
- No action. The light only shows the selected setting.
- To test the dehumidistat, lower the set point until the light starts blinking and the fan goes to high.
Settings for these units
HRV maintenance intervals · RNC
| Item | How often |
|---|---|
| Outside hoods and bird screen | Monthly (more in winter for snow and frost) |
| Filters (washable) | 4 times a year |
| Core | Twice a year |
| Motors | No maintenance |
| Condensate drain line and P-trap | Once a year |
| Ductwork | Once a year if needed |
| Inside of cabinet wipe-down | Twice a year |
Turn off power at the disconnect before any service.
Models that show this code
1 model in RNC
Other codes on the same units
- 0 Fan speed 0 = standby (DXPL02)
- Dehumidistat light flashing Dehumidistat calling, unit on high speed
- OFF Dehumidistat turned off (DXPL02)
- Repeater LED flashing green Wireless repeater: medium link
- Repeater LED red Wireless repeater: no link to main control
- Repeater LED solid green Wireless repeater: strong link
- Service indicator Maintenance due (DXPL02)
- Timer battery LED red Wireless timer battery low
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lifebreath RNC5-ES Homeowner's Guide (69-RNC5-OWNERS 012616), Ventilation Controls BC02 / BC03, p. 5-6. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.