Lifebreath · Hrv
0 Fan speed 0 = standby (DXPL02)
What the display is showing
Speed 0 on the DXPL02 screen means standby. The HRV has power but the fans are off until a timer or the dehumidistat calls for ventilation.
Applies to: 99-DXPL02 digital control
Good to know
- Fan speed set to 0 by the user
What to do
- If the customer says the HRV does not run, check the screen for speed 0 before going further.
- Press the Fan button to pick a speed from 1 to 5.
Settings for these units
HRV maintenance intervals · RNC
| Item | How often |
|---|---|
| Outside hoods and bird screen | Monthly (more in winter for snow and frost) |
| Filters (washable) | 4 times a year |
| Core | Twice a year |
| Motors | No maintenance |
| Condensate drain line and P-trap | Once a year |
| Ductwork | Once a year if needed |
| Inside of cabinet wipe-down | Twice a year |
Turn off power at the disconnect before any service.
Models that show this code
1 model in RNC
Other codes on the same units
- Dehumidistat light flashing Dehumidistat calling, unit on high speed
- Dehumidistat light steady Dehumidistat satisfied
- OFF Dehumidistat turned off (DXPL02)
- Repeater LED flashing green Wireless repeater: medium link
- Repeater LED red Wireless repeater: no link to main control
- Repeater LED solid green Wireless repeater: strong link
- Service indicator Maintenance due (DXPL02)
- Timer battery LED red Wireless timer battery low
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lifebreath RNC5-ES Homeowner's Guide (69-RNC5-OWNERS 012616), Digital Control DXPL02, p. 8; Additional Information, p. 15. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.