ICP · Heat pump
8 Welded contactor
What the control is telling you
Compressor runs all the time.
Applies to: ICP N4H3 R-410A split heat pump (manual 428 01 5103 02); Comfort Alert codes apply only to units factory-fitted with the Comfort Alert module
Likely causes
- Contactor welded closed
- Thermostat demand wire not connected to the module
Test and repair steps
- Warning: Turn off power at the disconnect - the compressor may run with no call.
- Check contactor contacts; replace if welded.
- Check the Y demand wire is connected to the Comfort Alert module.
Settings for these units
- Outdoor unit clearances · ICP N4H3 Heat Pump
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP N4H3 Installation Instructions 428 01 5103 02, Comfort Alert Diagnostics Codes (Figure 18), p.20. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.