ICP heat pump error codes

13 codes (11 faults, 2 normal display and menu codes), plus 1 settings tables.

CodeMeaningSeverity / type
1Long run timeMedium
2System pressure tripHigh
3Short cyclingMedium
4Locked rotorHigh
5Open circuitHigh
6Open start circuitHigh
7Open run circuitHigh
8Welded contactorCritical
9Low voltageMedium
Defrost SPEEDUP testDefrost board SPEEDUP pin testMenu / mode display
Green POWER LEDComfort Alert green POWER LED - module poweredNormal status
Red TRIP LEDComfort Alert TRIP - Y1 call but compressor not runningHigh
TRIP + ALERT flashing togetherControl voltage too lowMedium

Settings and specs

Outdoor unit clearances

Clearances · ICP N4H3 Heat Pump

LocationMinimum
Above unit (discharge)48 in. (1.2 m)
Each coil side (intake)18 in. (457 mm)
One coil side, reduced (unit to structure)6 in. (152 mm)
Control box corner and service panel24 in. (610 mm)
Between side-by-side units18 in. (457 mm)
Roof overhang above unit (with gutters)48 in. (1.2 m) vertical
  • Small objects (post, fence end): clearance about equal to the object width.
  • Do not install under an overhang without gutters.

Source: ICP N4H3 Installation Instructions 428 01 5103 02, Clearances, PDF p.3 (printed p.2)

Models covered

N4H3

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.