ICP · Heat pump

4 Locked rotor

High severity ICP N4H3 Heat Pump

What the control is telling you

Compressor is not turning (locked rotor).

Applies to: ICP N4H3 R-410A split heat pump (manual 428 01 5103 02); Comfort Alert codes apply only to units factory-fitted with the Comfort Alert module

Likely causes

  • Failed run capacitor
  • Low line voltage
  • Excess liquid refrigerant in compressor
  • Seized compressor bearings

Test and repair steps

  1. Warning: Discharge capacitors before testing.
  2. Test the run capacitor; replace if failed.
  3. Measure line voltage at the unit under load; contact the utility if low at the disconnect.
  4. Check crankcase heater operation and for refrigerant flood-back.
  5. If capacitor and voltage are good, the compressor is likely seized - replace.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP N4H3 Installation Instructions 428 01 5103 02, Comfort Alert Diagnostics Codes (Figure 18), p.20. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.