ICP · Heat pump
Green POWER LED Comfort Alert green POWER LED - module powered
What the display is showing
On heat pumps fitted with the Comfort Alert diagnostic module, the green POWER LED lit means the module has 24 VAC power. Normal. The red TRIP and yellow ALERT LEDs only come on for a problem.
Applies to: ICP N4H3 heat pumps with Comfort Alert
Settings for these units
Outdoor unit clearances · ICP N4H3 Heat Pump
| Location | Minimum |
|---|---|
| Above unit (discharge) | 48 in. (1.2 m) |
| Each coil side (intake) | 18 in. (457 mm) |
| One coil side, reduced (unit to structure) | 6 in. (152 mm) |
| Control box corner and service panel | 24 in. (610 mm) |
| Between side-by-side units | 18 in. (457 mm) |
| Roof overhang above unit (with gutters) | 48 in. (1.2 m) vertical |
Small objects (post, fence end): clearance about equal to the object width.
Do not install under an overhang without gutters.
Models that show this code
1 model in ICP N4H3 Heat Pump
Other codes on the same units
- 5 Open circuit
- 6 Open start circuit
- 7 Open run circuit
- 8 Welded contactor
- 9 Low voltage
- Defrost SPEEDUP test Defrost board SPEEDUP pin test
- Red TRIP LED Comfort Alert TRIP - Y1 call but compressor not running
- TRIP + ALERT flashing together Control voltage too low
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP N4H3 Installation Instructions 428 01 5103 02, Figure 18 Comfort Alert status LEDs, p.19. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.