ICP · Heat pump

Defrost SPEEDUP test Defrost board SPEEDUP pin test

Menu / mode display ICP N4H3 Heat Pump

What the display is showing

With the unit heating and the defrost thermostat closed, shorting the SPEEDUP pins on the defrost board skips the remaining interval timer and forces a defrost. In normal operation the reversing valve shifts within 1 to 21 seconds. During defrost the outdoor fan stops and strip heat comes on. In the shortened test the defrost ends when the defrost thermostat opens at 65 F or the short timer ends (under 10 minutes).

Applies to: ICP N4H3 heat pumps

What to do

  1. Run the unit in heating mode with the defrost thermostat closed (or jumper the DFT terminals).
  2. Short the SPEEDUP pins with a screwdriver until the reversing valve shifts.
  3. Remove the short at once for a brief defrost, or keep it for 2+ seconds to go straight back to heating.

Settings for these units

Outdoor unit clearances · ICP N4H3 Heat Pump

LocationMinimum
Above unit (discharge)48 in. (1.2 m)
Each coil side (intake)18 in. (457 mm)
One coil side, reduced (unit to structure)6 in. (152 mm)
Control box corner and service panel24 in. (610 mm)
Between side-by-side units18 in. (457 mm)
Roof overhang above unit (with gutters)48 in. (1.2 m) vertical

Small objects (post, fence end): clearance about equal to the object width.

Do not install under an overhang without gutters.

Models that show this code

1 model in ICP N4H3 Heat Pump

N4H3

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP N4H3 Installation Instructions, Defrost System (defrost control board and testing). Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.