Goodman · Air conditioner

L8 Low line voltage

High severity Goodman/Amana ComfortNet ASXC/GSXC/DSXC

What the control is telling you

Line voltage measured below 185 VAC. Unit may appear to run normally or the compressor may be off on its protector. Clears when voltage goes back above 185 VAC.

Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18

Likely causes

  • Low supply voltage
  • Undersized or long supply wiring, loose connections

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Measure line voltage at the unit during compressor start and run.
  3. Check breakers, fuses and connections; confirm supply matches the rating plate.
  4. Correct wiring or contact the utility if the supply is low.

Models that show this code

23 models in Goodman/Amana ComfortNet ASXC/GSXC/DSXC

ASXC160241ASXC160361ASXC160481ASXC160601ASXC180241ASXC180361ASXC180481ASXC180601DSXC160241DSXC160361DSXC160481DSXC160601DSXC180361DSXC180481DSXC180601GSXC160241GSXC160361GSXC160481GSXC160601GSXC180241GSXC180361GSXC180481GSXC180601

Other codes on the same units

  • d2 System mismatch - indoor unit cannot supply required airflow
  • d3 Configuration mismatch - shared data does not match hardware
  • d4 Shared data from the loader rejected
  • E5 Outdoor control low-voltage fuse open
  • L1 Lockout - low pressure switch tripped 3 times
  • L2 Lockout - high pressure switch tripped 3 times
  • L7 Lockout - open run circuit detected 4 times
  • P0 Compressor protector open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.