Goodman · Air conditioner
E5 Outdoor control low-voltage fuse open
What the control is telling you
The 24 V fuse on the outdoor control has blown, so the A/C or heat pump does not run.
Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18
Likely causes
- Short to ground or between conductors in the low-voltage wiring
Test and repair steps
- Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
- Find the short first check thermostat/communication wires for nicks, pinches against sheet metal, and wiring at the contactor coil, reversing valve and pressure switches.
- Replace the fuse only with a 3 A automotive (blade) fuse.
- Restore power and confirm the code clears; if the fuse blows again, isolate circuits one at a time until the short is found.
Models that show this code
23 models in Goodman/Amana ComfortNet ASXC/GSXC/DSXC
Other codes on the same units
- d1 Invalid shared data on the network
- d2 System mismatch - indoor unit cannot supply required airflow
- d3 Configuration mismatch - shared data does not match hardware
- d4 Shared data from the loader rejected
- L1 Lockout - low pressure switch tripped 3 times
- L2 Lockout - high pressure switch tripped 3 times
- L7 Lockout - open run circuit detected 4 times
- L8 Low line voltage
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.