Goodman · Air conditioner
d3 Configuration mismatch - shared data does not match hardware
What the control is telling you
The shared data sent to the outdoor control does not fit the hardware the control is installed in.
Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18
Likely causes
- Shared data for a different model/size was loaded
Test and repair steps
- Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
- Compare the model on the rating plate with the shared data loaded; reload the correct data with the BTSDL01.
- Plug the BTSDL01 in BEFORE turning power on; after the data loads, turn power off before unplugging it.
- If the system cannot be run as communicating, wire it as a legacy 24 V system instead.
Models that show this code
23 models in Goodman/Amana ComfortNet ASXC/GSXC/DSXC
Other codes on the same units
- b9 Indoor airflow lower than requested
- d0 No shared data on the network
- d1 Invalid shared data on the network
- d2 System mismatch - indoor unit cannot supply required airflow
- d4 Shared data from the loader rejected
- E5 Outdoor control low-voltage fuse open
- L1 Lockout - low pressure switch tripped 3 times
- L2 Lockout - high pressure switch tripped 3 times
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.