Goodman · Air conditioner

L1 Lockout - low pressure switch tripped 3 times

High severity Goodman/Amana ComfortNet ASXC/GSXC/DSXC

What the control is telling you

The low pressure switch opened 3 times during the same thermostat call, so the outdoor control locked out the compressor and fan.

Applies to: Communicating 2-stage condensers and heat pumps with the PCBHR104 or PCBHR105 outdoor control (7-segment display): ASXC16/18, GSXC16/18, DSXC16/18, ASZC16/18, GSZC16/18, DSZC16/18

Likely causes

  • Low refrigerant charge
  • Restricted liquid line (drier, kinked line)
  • Indoor blower motor failed or not running
  • Thermostat set very low
  • Faulty low pressure switch

Test and repair steps

  1. Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
  2. Check charge with superheat/subcooling and correct it; leak check if low.
  3. Look for a temperature drop across the liquid line drier or any kinks - repair restrictions.
  4. Confirm the indoor blower runs at the right speed and filters/coil are clean.
  5. Check the thermostat set point.
  6. Test the low pressure switch (opens about 21 psig, closes about 50 psig).
  7. To reset a lockout, interrupt the 24 VAC supply to the outdoor control (power cycle the low voltage), then retest.

Models that show this code

23 models in Goodman/Amana ComfortNet ASXC/GSXC/DSXC

ASXC160241ASXC160361ASXC160481ASXC160601ASXC180241ASXC180361ASXC180481ASXC180601DSXC160241DSXC160361DSXC160481DSXC160601DSXC180361DSXC180481DSXC180601GSXC160241GSXC160361GSXC160481GSXC160601GSXC180241GSXC180361GSXC180481GSXC180601

Other codes on the same units

  • d2 System mismatch - indoor unit cannot supply required airflow
  • d3 Configuration mismatch - shared data does not match hardware
  • d4 Shared data from the loader rejected
  • E5 Outdoor control low-voltage fuse open
  • L2 Lockout - high pressure switch tripped 3 times
  • L7 Lockout - open run circuit detected 4 times
  • L8 Low line voltage
  • P0 Compressor protector open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Goodman ComfortNet ASXC/GSXC/DSXC, ASZC/GSZC/DSZC, AVPTC/MBVC service manual, Unitary Diagnostic Codes PCBHR104 p.71-77 and PCBHR105 p.78-84. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.