Goodman · Air conditioner
CoreSense solid red Solid red TRIP - call present but compressor not running
What the control is telling you
Red LED steady: the module sees a Y demand but the compressor is not running.
Applies to: Copeland CoreSense 3-wire module: Amana/Deluxe R-410A ASX, ASZ, DSX, DSZ units and Amana R-32 ALXS / ALZS units
Likely causes
- Compressor protector open (check head pressure and compressor voltage)
- Outdoor disconnect open
- Compressor breaker or fuses open
- Broken wire or poor connector
- High pressure switch open (if fitted)
- Contactor failed open
Test and repair steps
- Warning: Kill power to the outdoor unit before touching wiring, the compressor terminals or the control.
- Check disconnect, breaker and fuses.
- Check contactor coil voltage and contacts.
- Check head pressure and compressor supply voltage; let a hot compressor cool.
- Check the high pressure switch and wiring.
Models that show this code
150 models in Goodman/Amana R-32 GLXS/ALXS, Goodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)
Other codes on the same units
- Comfort Alert last alert recall Last alert code replayed after power-up
- CoreSense 1 Yellow 1 flash - long run time (low side)
- CoreSense 2 Pressure trip - yellow 2 flashes (red 2 = lockout)
- CoreSense 3 Short cycling / pressure switch cycling - yellow 3 (red 3 = lockout)
- CoreSense 4 Locked rotor - yellow 4 (red 4 = lockout)
- CoreSense 5 Moderate run trip - yellow 5 (red 5 = lockout)
- CoreSense 9 Red 9 flashes - PROT output overcurrent
- CoreSense solid yellow Solid yellow RUN - module powered, operating normally
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), CoreSense Diagnostics Table p.21-22 and Quick Reference Table p.23; Goodman RS6200006r103 R-410A ASX/GSX/DSX/ASZ/GSZ/DSZ service (text export) (Goodman_R_410A_ASX_GSX_DSX_A_C_and_ASZ_GSZ_DSZ_HP_covers_GSX_GSZ_lines_GSXH5_GSZH5_service.txt section Diagnostics Table: Coresense Module / Table 1 Quick Reference). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.