Goodman · Air conditioner
CoreSense 5 Moderate run trip - yellow 5 (red 5 = lockout)
What the control is telling you
Compressor ran 15 min to 18 h, then tripped for longer than 7 min. Red 5 flashes = lockout after 4 trips in a row or 10 total.
Applies to: Copeland CoreSense 3-wire module: Amana/Deluxe R-410A ASX, ASZ, DSX, DSZ units and Amana R-32 ALXS / ALZS units
Likely causes
- Indoor blower not running
- Metering device stuck or TXV bulb badly mounted
- Poor airflow over the outdoor coil
- Low charge
Test and repair steps
- Check indoor blower, its relay, capacitor, motor, wiring and indoor board.
- Check the TXV bulb and metering device.
- Clean and clear the outdoor coil.
- Check refrigerant charge.
Models that show this code
150 models in Goodman/Amana R-32 GLXS/ALXS, Goodman/Amana R-410A GSX/ASX/DSX (ANX/SSX/VSX)
Other codes on the same units
- Comfort Alert last alert recall Last alert code replayed after power-up
- CoreSense 1 Yellow 1 flash - long run time (low side)
- CoreSense 2 Pressure trip - yellow 2 flashes (red 2 = lockout)
- CoreSense 3 Short cycling / pressure switch cycling - yellow 3 (red 3 = lockout)
- CoreSense 4 Locked rotor - yellow 4 (red 4 = lockout)
- CoreSense 9 Red 9 flashes - PROT output overcurrent
- CoreSense solid red Solid red TRIP - call present but compressor not running
- CoreSense solid yellow Solid yellow RUN - module powered, operating normally
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), CoreSense Diagnostics Table p.21-22 and Quick Reference Table p.23; Goodman RS6200006r103 R-410A ASX/GSX/DSX/ASZ/GSZ/DSZ service (text export) (Goodman_R_410A_ASX_GSX_DSX_A_C_and_ASZ_GSZ_DSZ_HP_covers_GSX_GSZ_lines_GSXH5_GSZH5_service.txt section Diagnostics Table: Coresense Module / Table 1 Quick Reference). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.