Daikin · Water heater
UC UC: duplicate cascade unit address
What the control is telling you
Shown when two cascade units in the same system have the same address number.
Applies to: Cascade units in one system
Likely causes
- Two or more cascade units set to the same address
Test and repair steps
- Set each cascade unit to a unique address from 1 to 8 in ascending order.
- Recheck all cascade unit addresses in the system.
Other codes on the same units
- EC Low tank water temperature
- HJ Flow rate cannot be adjusted (cascade)
- JA High pressure sensor connector X32A disconnected
- JC Low pressure sensor connector X31A disconnected
- LC Inverter communication connectors disconnected
- UE Transmission to tank control board not established
- UF Incorrect water piping connection
- UJ Active filter error
Sequence of operation
What the unit does around this code, step by step.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Mega-Q installation manual, p. 40. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.