Daikin · Water heater

HJ Flow rate cannot be adjusted (cascade)

Medium severity Mega-Q

What the control is telling you

Subdivision 07 (cascade unit): the proper water flow rate cannot be adjusted.

Applies to: Cascade unit

Likely causes

  • Gate valve not fully open
  • Strainer clogged
  • Water piping size or length not per selection procedure
  • Inlet pressure out of range
  • Air trapped in piping

Test and repair steps

  1. Make sure the gate valve is fully open.
  2. Clean the strainer if clogged.
  3. Confirm piping size and length match the selection procedure.
  4. Confirm inlet pressure is within range.
  5. Release air from the piping.

Other codes on the same units

  • P1 Power supply voltage imbalance
  • U1 Power wiring reverse phase or no power
  • U2 Power supply voltage error, imbalance or phase loss
  • EC Low tank water temperature
  • JA High pressure sensor connector X32A disconnected
  • JC Low pressure sensor connector X31A disconnected
  • LC Inverter communication connectors disconnected
  • UC UC: duplicate cascade unit address

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin Mega-Q installation manual, p. 50. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.