Daikin · Water heater
U1 Power wiring reverse phase or no power
What the control is telling you
Subdivisions 01 and 05: reverse phase (two of three phases exchanged). Subdivisions 04 and 06: no power supplied to the unit, including phase loss. 01 and 04 are cascade unit, 05 and 06 are heat source unit.
Applies to: Cascade unit and heat source unit
Likely causes
- Two phases swapped (01, 05)
- No power or phase loss to unit (04, 06)
Test and repair steps
- Check that the power wiring of the affected unit is connected correctly.
- Correct any wiring mistakes, including swapped phases or open phases.
Other codes on the same units
- J7 J7 subcodes 13 and 14: cascade unit X30A thermistor disconnected
- J8 J8 subcode 02
- J9 J9 subcode 02
- P1 Power supply voltage imbalance
- U2 Power supply voltage error, imbalance or phase loss
- EC Low tank water temperature
- HJ Flow rate cannot be adjusted (cascade)
- JA High pressure sensor connector X32A disconnected
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin Mega-Q installation manual, p. 49. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.