Daikin · Heat pump

E20 Outdoor EEV fault

High severity Daikin FIT DH6VS/DH7VSA

What the control is telling you

Thermostat shows 20, outdoor board display shows E20. The control sees a problem with the outdoor electronic expansion valve.

Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)

Likely causes

  • Outdoor EEV coil unplugged
  • Bad outdoor EEV coil
  • Bad control board

Test and repair steps

  1. Kill power at the disconnect before opening the control box or touching wiring.
  2. Check the outdoor EEV coil plug and the coil. Repair or replace it.
  3. If the coil is good, replace the control board.

Models that show this code

11 models in Daikin FIT DH6VS/DH7VSA

DH6VS*181DH6VS*241DH6VS*301DH6VS*361DH6VS*421DH6VS*481DH6VS*601DH7VSA2410DH7VSA3610DH7VSA4210DH7VSA4810

Other codes on the same units

  • E15 Repeated low pressure faults (critical)
  • E17 Repeated compressor faults (critical)
  • E18 Control board may need replacing (outdoor fan drive)
  • E19 Repeated outdoor fan / board faults (critical)
  • E21 Repeated low discharge superheat faults
  • E22 Repeated high discharge temperature faults
  • E23 Discharge temperature sensor out of range
  • E24 High pressure switch open

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.43 (printed page). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.