Daikin · Heat pump

E22 Repeated high discharge temperature faults

High severity Daikin FIT DH6VS/DH7VSA

What the control is telling you

Thermostat shows 22, outdoor board display shows E22. Discharge temperature keeps going too high. A discharge thermistor that is off the pipe or in the wrong spot can also cause this.

Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)

Likely causes

  • Discharge thermistor bad, unplugged, off the pipe or in the wrong spot
  • Compressor shell too hot
  • Low charge
  • Too much refrigerant
  • Bad compressor

Test and repair steps

  1. Kill power at the disconnect before opening the control box or touching wiring.
  2. Check the discharge thermistor resistance and plug.
  3. Make sure the discharge thermistor is on the pipe in the right spot.
  4. Check the charge and adjust.
  5. Check the compressor.

Models that show this code

11 models in Daikin FIT DH6VS/DH7VSA

DH6VS*181DH6VS*241DH6VS*301DH6VS*361DH6VS*421DH6VS*481DH6VS*601DH7VSA2410DH7VSA3610DH7VSA4210DH7VSA4810

Other codes on the same units

  • E18 Control board may need replacing (outdoor fan drive)
  • E19 Repeated outdoor fan / board faults (critical)
  • E20 Outdoor EEV fault
  • E21 Repeated low discharge superheat faults
  • E23 Discharge temperature sensor out of range
  • E24 High pressure switch open
  • E25 Outdoor air temperature sensor open or shorted
  • E26 Pressure sensor not responding

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.43 (printed page). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.